Model |
DA12(24/48/110/230)-5KO-D |
According to standards: GB/T18802.11(IEC61643-11) |
Level 3/Category III
|
Nominal DC voltage (Un) |
5V~12V/24V/48V/110V/230V |
DC maximum continuous operating voltage (Uc) |
18V/36V/60V/150V/320V |
Nominal discharge current (8/20μs) [ln] |
5KA |
Maximum discharge current (8/20μs) [lmax] |
10KA |
Voltage protection level (Up) |
10KA |
Voltage protection level@5KA (Up) |
0.4KV/0.4KV/0.8KV/1KV/1.5KV |
Response time (t) |
≤25ns |
External backup fuse |
built-in |
Leakage current |
- |
Operating temperature range (Tu) |
-40℃~+80°C |
Working status/fault indication |
red/none |
Maximum load current |
1A |
Number of ports |
2 |
Minimum installation conductor cross-sectional area |
0.5mm² single strand/multiple strands |
Maximum installation conductor cross-sectional area |
2.5mm² (Line side) /4mm² (PE Side) single strand/multiple strands |
Installation method |
35mm DIN rail according to EN 60715 |
Shell material |
Gray thermoplastic, UL94 V-0 |
Installation Location |
Indoor |
Protection level |
IP20 |
Size |
1.35 digital analog, DIN 43880 |
Relative humidity |
≤95% no condensation |