Model | D1000-20K-PV3P | D1200-20K-PV3P | D1500-20K-PV3P |
According to standards: GB/T18802.31/IEC61643-31 | Level 2/Category II |
Nominal DC voltage (Un) | 1000V | 1200V | 1500V |
DC maximum continuous operating voltage (Uc) | 1000V | 1200V | 1500V |
Nominal discharge current (8/20μs) [ln] | 20KA |
Maximum discharge current (8/20μs) [lmax] | 40KA |
Voltage protection level (Up) | 3.6KV | 4.2KV | 4.6KV |
Voltage protection level@5KA (Up) | - |
Response time (t) | ≤25ns |
External backup fuse | 80A gG |
Leakage current | ≤20A |
Operating temperature range (Tu) | -40°C~+80°C |
Working status/fault indication | green/red |
Minimum installation conductor cross-sectional area | 1.5mm² solid wire/flexible wire |
Maximum installation conductor cross-sectional area | 35mm² stranded wire/25mm² flexible wire |
Installation method | 35mm DIN rail according to EN 60715 |
Shell material | Gray thermoplastic, UL94 V-0 |
Installation Location | Indoor |
Protection level | IP20 |
Size | 3 digital analog, DIN 43880 |
Relative humidity | ≤95% no condensation |
Remote signaling contact type (optional) | floating switch electric shock |
AC load capacity | 250V/0.5A |
DC load capacity | 250V/0.1A;125V/0.2A, 75V/0.5A |
Cross-sectional area of remote signaling terminal | Maximum 1.5mm² solid wire/flexible wire |