Model |
A385-10K-1P(2P/3P/4P)
|
According to standards: GB/T18802.11(IEC61643-11) |
Level 3/Category II
|
Nominal DC voltage (Un) |
230V/400V(50/60HZ) |
DC maximum continuous operating voltage (Uc) |
385V(50/60HZ) |
Nominal discharge current (8/20μs) [ln] |
10KA |
Maximum discharge current (8/20μs) [lmax] |
20KA |
Voltage protection level (Up) |
1.5KA |
Voltage protection level@5KA (Up) |
1.3KV |
Response time (t) |
≤25ns |
External backup fuse |
40A Gg/20A/SCB-80
|
Leakage current |
≤20μA |
Operating temperature range (Tu) |
-40℃~+80°C |
Working status/fault indication |
green/red |
Minimum installation conductor cross-sectional area |
1.5mm²; solid wire/flexible wire |
Maximum installation conductor cross-sectional area |
35mm²; stranded wire/25mm²; flexible wire |
Installation method |
35mm DIN rail according to EN 60715 |
Shell material |
Gray thermoplastic, UL94 V-0 |
Installation Location |
Indoor |
Protection level |
IP20 |
Size |
1/2/3/4 digital analog, DIN 43880 |
Relative humidity |
≤95% no condensation |
Remote signaling contact type (optional) |
floating switch electric shock |
AC load capacity |
250V/0.5A |
DC load capacity |
250V/0.1A;125V/0.2A, 75V/0.5A |
Cross-sectional area of remote signaling terminal |
Maximum1.5mm² solid wire/flexible wire |