Model |
ACE(AE/DCE/DE)-5KO
|
According to standards: GB/T18802.11(IEC61643-11) | Level 3/Category III
|
Nominal DC voltage (Un) |
24V[D]/ 230V[AJ(50/60Hz)/12V[CJ/5V[E]
|
DC maximum continuous operating voltage (Uc) |
36V[D]/ 320V[AJ(50/60Hz)/18V[C]/8V[E]
|
Nominal discharge current (8/20μs) [ln] | 5KA |
Maximum discharge current (8/20μs) [lmax] | 10KA |
Voltage protection level (Up) | 10KA |
Voltage protection level@5KA (Up) | Power supply: 1.5KV[A]/1KV[D], signal: 80V (line to line) 1750V (Line to ground) [C] 65V (line to line) /900V (line to ground) TE] |
Response time (t) | ≤25ns |
External backup fuse | built-in(Power A/D) |
Leakage current | - |
Operating temperature range (Tu) | -40℃~+70°C |
Working status/fault indication | green/none |
Maximum load current | 1A |
Insertion loss | ≤0.5dB[C]/[E] |
Minimum installation conductor cross-sectional area | 0.5mm² single strand/multiple strands |
Maximum installation conductor cross-sectional area | 4mm² single strand/multiple strands |
Installation method | 35mm DIN rail according to EN 60715 |
Shell material | Gray thermoplastic, UL94 V-0 |
Installation Location | Indoor |
Protection level | IP20 |
Size | 2 digital analog, DIN 43880 |
Relative humidity | ≤95% no condensation |