Model | DA12(24/48/110/230)-5KO-A |
According to standards: GB/T18802.11(IEC61643-11) | Level 3/Category III
|
Nominal DC voltage (Un) | 5V~12V/24V/48V/110V/230V |
DC maximum continuous operating voltage (Uc) | 18V/36V/60V/150V/320V |
Nominal discharge current (8/20μs) [ln] | 5KA |
Maximum discharge current (8/20μs) [lmax] | 10KA |
Voltage protection level (Up) | 10KA |
Voltage protection level@5KA (Up) | 0.4KV/0.4KV/0.8KV/1KV/1.5KV |
Response time (t) | ≤25ns |
External backup fuse | built-in |
Leakage current | - |
Operating temperature range (Tu) | -40℃~+80°C |
Working status/fault indication | green/none |
Minimum installation conductor cross-sectional area | 1mm² single strand/multiple strands |
Maximum installation conductor cross-sectional area | 4mm² single strand/multiple strands |
Installation method | 35mm DIN rail according to EN 60715 |
Shell material | Gray thermoplastic, UL94 V-0 |
Installation Location | Indoor |
Protection level | IP20 |
Size | 1.5 digital analog, DIN 43880 |
Relative humidity | ≤95% no condensation |
Remote signaling contact type (optional) | Thermal fuse |
AC load capacity | 250V/0.5A |
DC load capacity | 250V/0.1A;125V/0.2A, 75V/0.5A |
Cross-sectional area of remote signaling terminal | Maximum1.5mm² solid wire/flexible wire |